CVE-2026-129713
Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler
CVE-2026-129713 is a stack overflow in Danfoss AK-SM8xxA (CVSS 9.8, Critical).
No known exploitation. EPSS puts it in the 81st percentile. A vendor fix is available.
No public exploit knownFixVendor fixNo build named by the sources
No ready-made check. Neither Nuclei nor OpenVAS has one for this CVE yet.
What to do
The vendor has published a fix. Version details are below where the sources state them.
- Danfoss AK-SM8xxAAffected: ≤ 5.4.0Upgrade to: after 5.4.0Stated by: CVE record
Versions as the sources state them. Full version matrix after sign-in
Steps
Written by AI from the record- Check whether you operate a Danfoss AK-SM8xxA controller and whether it is reachable from the public internet.
- If exposed, immediately remove it from direct internet access — place it behind a secure VPN or isolate it on a protected internal network.
- Enable or keep the device's 'Strict mode' setting if available, since Danfoss plans to remove the option to disable it.
- Apply Danfoss AK-SM 8xxA software version 5.5.x once released, which will contain the fix.
- Follow Danfoss's manual guidance on network segmentation for these controllers until the patch is installed.
Coverage timeline
2 publishersCISA warned of an unpatched Danfoss AK-SM 8xxA buffer overflow (CVE-2026-129713) and linked recent supermarket refrigeration disruptions to ongoing compromise activity.
Sourced from public security reporting — each date is when it was published, not when it happened.
What it is
From the CVE record
A stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability.
In plain language
Written by AI from the recordThis is a serious remote-takeover flaw in Danfoss AK-SM8xxA refrigeration/building controllers that requires no password to trigger, and if your unit is reachable from the internet you should act now.
Unauthenticated stack-based buffer overflow (CWE-121) in a CGI handler of Danfoss AK-SM8xxA controllers allows remote attackers to send crafted HTTP/S POST requests that corrupt memory, crash the webserver, and potentially achieve arbitrary code execution with webserver privileges.
If you're affected
- Full controller takeover
- Refrigeration/HVAC system disruption
- Food/product spoilage risk
- Remote code execution risk
- Device crash / downtime
Exploitation
Where each signal puts this CVE on the scale from published to confirmed exploited.
- CISA KEV
Not in the catalog. CISA has not confirmed exploitation.
- Public exploits
No public exploit or proof of concept found in the sources we track.
- EPSS
2.0% chance of exploitation activity in the next 30 days, which ranks it in the 81st percentile of scored CVEs.
Exploit Prediction Scoring System, FIRST.org. A probability, not a confirmation.
- Attention now
Sustained, driven by in-the-wild reports.
Lifecycle
9 events over 4 days, from the signal feeds we watch.
- Patch availableworkaround available, record updated
- Patch availableworkaround available, published, weakness classified, att&ck mapped, record updated
Affected products
Technical detail
CVSS 3.1 vector
Open in the CVSS calculatorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Scored 9.8 by csaf.
How it is reached
- Attack Vector NetworkExploitable remotely over the network without any special conditions
- Attack Complexity LowNo special conditions — the attack can be reliably reproduced
- Privileges Required NoneNo authentication required — anyone can exploit this
- User Interaction NoneNo user interaction needed — fully automated exploitation
Scope
- Scope UnchangedImpact is limited to the vulnerable component itself
Impact if exploited
- Confidentiality HighTotal information disclosure — all data in the component is compromised
- Integrity HighTotal loss of integrity — attacker can modify any data in the component
- Availability HighTotal denial of service — the component is completely unavailable
Weaknesses
ATT&CK techniques
Mapped from the weaknesses above (CWE to ATT&CK), not observed in attacks.
- Privilege EscalationT1068Exploitation for Privilege Escalationhigh confidence
Sources
References in the record
- danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2026-12-01/
- raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-328-03.json
- cisa.gov/news-events/ics-advisories/icsa-26-328-03
And 15 more references. See all after sign-in
In the news
Questions about CVE-2026-129713
- Is CVE-2026-129713 being exploited?
- No exploitation is confirmed and no public exploit is known. EPSS puts the chance of exploitation in the next 30 days at 2.0%.
- Which versions are affected by CVE-2026-129713?
- AK-SM8xxA: ≤ 5.4.0.
- How do I fix or mitigate CVE-2026-129713?
- The vendor has published a fix. The advisory is on danfoss.com.
Last updated
Related articles
All articlesWatch the software you run.
My Stack ranks new CVEs for your products by real-world exploitation, so the next serious one reaches you without reading every advisory.
We'll flag the next CVE, public exploit or patch for AK-SM8xxA, not every advisory.
A free account adds
- The full version matrix and every affected product
- Exploit links, proofs of concept and Metasploit modules
- Email alerts for the products you watch
- The same data over REST API, MCP and CLI