CVE-2026-11826
OpenPLC_v3 Heap-Based Buffer Overflow in Modbus Master getData()
No known exploitation. EPSS puts it in the 54th percentile. No fix published yet.
What to do
No fixed build or workaround is published yet. Limit exposure and watch for a patch.
- openplcproject OpenPLC_v3Affected: ≤ b470206Upgrade to: after b470206Stated by: CVE record
Versions as the sources state them. Full version matrix after sign-in
What it is
From the CVE record
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.
In plain language
No plain-language summary for this CVE yet.
Exploitation
Where each signal puts this CVE on the scale from published to confirmed exploited.
- CISA KEV
Not in the catalog. CISA has not confirmed exploitation.
- Public exploits
No public exploit or proof of concept found in the sources we track.
- EPSS
0.8% chance of exploitation activity in the next 30 days, which ranks it in the 54th percentile of scored CVEs.
Exploit Prediction Scoring System, FIRST.org. A probability, not a confirmation.
Lifecycle
7 events over 98 days, from the signal feeds we watch.
- Record updated
- Record updated
- Record updated
- Publishedweakness classified, att&ck mapped, record updated
Affected products
Technical detail
CVSS 3.1 vector
Open in the CVSS calculatorCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Scored 8.8 by NVD.
How it is reached
- Attack Vector NetworkExploitable remotely over the network without any special conditions
- Attack Complexity LowNo special conditions — the attack can be reliably reproduced
- Privileges Required LowRequires basic user-level privileges
- User Interaction NoneNo user interaction needed — fully automated exploitation
Scope
- Scope UnchangedImpact is limited to the vulnerable component itself
Impact if exploited
- Confidentiality HighTotal information disclosure — all data in the component is compromised
- Integrity HighTotal loss of integrity — attacker can modify any data in the component
- Availability HighTotal denial of service — the component is completely unavailable
Weaknesses
ATT&CK techniques
Mapped from the weaknesses above (CWE to ATT&CK), not observed in attacks.
- Privilege EscalationT1068Exploitation for Privilege Escalationhigh confidence
Sources
Watch the software you run.
My Stack ranks new CVEs for your products by real-world exploitation, so the next serious one reaches you without reading every advisory.
We'll flag the next CVE, public exploit or patch for OpenPLC_v3, not every advisory.
A free account adds
- The full version matrix and every affected product
- Exploit links, proofs of concept and Metasploit modules
- Email alerts for the products you watch
- The same data over REST API, MCP and CLI