CVE Tools

CVE-2020-7540

CVE-2020-7540 is a missing auth in Schneider-electric Modicon M340 BMXP341000 Firmware (CVSS 9.8, Critical).

No known exploitation. EPSS puts it in the 84th percentile. Fixed in 3.30.

Check it yourself

No ready-made check. Neither Nuclei nor OpenVAS has one for this CVE yet.

Request a scan

Published Updated Sources: CVE.org, NVD, BDU

What to do

Find your product and version, then upgrade to the build on the right.

  • n/a Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication ModulesAffected: Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium…Upgrade to: not statedStated by: CVE record
  • Schneider-electric Modicon M340 Bmxp341000 FirmwareAffected: < 3.30Upgrade to: 3.30Stated by: NVD
  • Schneider-electric Modicon M340 Bmxp342000 FirmwareAffected: < 3.30Upgrade to: 3.30Stated by: NVD
  • Schneider-electric Modicon M340 Bmxp3420102 FirmwareAffected: < 3.30Upgrade to: 3.30Stated by: NVD
  • Schneider-electric Modicon M340 Bmxp3420102cl FirmwareAffected: < 3.30Upgrade to: 3.30Stated by: NVD

Versions as the sources state them. 23 more products have version data. Full version matrix after sign-in

What it is

From the CVE record

A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.

In plain language

No plain-language summary for this CVE yet.

Exploitation

Where each signal puts this CVE on the scale from published to confirmed exploited.

EPSS84th
CISA KEV

Not in the catalog. CISA has not confirmed exploitation.

Public exploits

No public exploit or proof of concept found in the sources we track.

EPSS

2.3% chance of exploitation activity in the next 30 days, which ranks it in the 84th percentile of scored CVEs.

Exploit Prediction Scoring System, FIRST.org. A probability, not a confirmation.

Lifecycle

5 events over 1441 days, from the signal feeds we watch.

  1. Patch availablerecord updated
  2. Publishedweakness classified, att&ck mapped

Affected products

Technical detail

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Scored 9.8 by NVD.

How it is reached

  • Attack Vector NetworkExploitable remotely over the network without any special conditions
  • Attack Complexity LowNo special conditions — the attack can be reliably reproduced
  • Privileges Required NoneNo authentication required — anyone can exploit this
  • User Interaction NoneNo user interaction needed — fully automated exploitation

Scope

  • Scope UnchangedImpact is limited to the vulnerable component itself

Impact if exploited

  • Confidentiality HighTotal information disclosure — all data in the component is compromised
  • Integrity HighTotal loss of integrity — attacker can modify any data in the component
  • Availability HighTotal denial of service — the component is completely unavailable

Weaknesses

ATT&CK techniques

Mapped from the weaknesses above (CWE to ATT&CK), not observed in attacks.

Sources

Questions about CVE-2020-7540

Is CVE-2020-7540 being exploited?
No exploitation is confirmed and no public exploit is known. EPSS puts the chance of exploitation in the next 30 days at 2.3%.
Which versions are affected by CVE-2020-7540?
Modicon M340 BMXP341000 Firmware: < 3.30. Modicon M340 BMXP342000 Firmware: < 3.30. Modicon M340 BMXP3420102 Firmware: < 3.30. 25 more products are listed in the record.
How do I fix or mitigate CVE-2020-7540?
Upgrade to 3.30 or later. The advisory is on download.schneider-electric.com.

Last updated

Watch the software you run.

My Stack ranks new CVEs for your products by real-world exploitation, so the next serious one reaches you without reading every advisory.

We'll flag the next CVE, public exploit or patch for Schneider-electric, not every advisory.